Stranded Copper Bare Wire А, АС, М
Home » Cable Products » Stranded Copper Bare Wire А, АС, М
Copper wire, which is a product of our own production, is manufactured on modern equipment in accordance with the quality standards TS-3 and TS EN 13602 and GOST-839-80. It can be used for various purposes, such as overhead power lines, ground wires, and others. It has excellent electrical conductivity, low resistance and good stability to overloads and heating. And the service life of the wires is at least 45 years.
Wire brand | Code of PQD | Wire construction | Preferred area of use |
m | 35 1111 | The wire consisting of one or twisted from several copper wires | In the atmosphere of air types II and III on land and sea of all macroclimatic areas according to GOST 15150 performance of moderately cold climate |
A | 35 1141 | Wire twisted from aluminum wires | In the atmosphere of air types I and II, provided that the atmosphere in the atmosphere of sulfur dioxide is not more than 150 mg/m2 day (1.5 mg/m3) on land, all macroclimatic areas according to GOST 15150 of the performance of MCC, except TV and TS |
AC | 35 1151 | Wire consisting of a steel core and aluminum wires | In the atmosphere of air types I and II, provided that the atmosphere in the atmosphere of sulfur dioxide is not more than 150 mg/m2 day (1.5 mg/m3) on land, all macroclimatic areas according to GOST 15150 of the performance of MCC, except TS and TV |
Nominal cross-section of the conductive part of the wire, mm2 | Construction length, m, not less, wire marks |
| M | A | AC |
4 | 2200 | – | – |
6 | 1500 | – | – |
10 | 900 | – | 3000 |
16 | 4000 | 4500 | 3000 |
25 | 3000 | 4000 | 3000 |
35 | 2500 | 4000 | 3000 |
50 | 2000 | 3500 | 3000 |
70 | 1500 | 2500 | 2000 |
95 | 1200 | 2000 | 1500 |
Nominal section, mm2 | Calculated data of A wire |
Section, mm2 | Wire diameter, mm | Electric resistance of 1 km of direct current wire at 20°С, Ohm, not more | Explosive effort of a wire, N, not less | Mass of 1 km of wire, kg |
(16) | 15,9 | 5,10 | 1,8007 | 3021 | 43,0 |
(25) | 24,9 | 6,40 | 1,1498 | 4500 | 68,0 |
(35) | 34,3 | 7,50 | 0,8347 | 5913 | 94,0 |
(50) | 49,5 | 9,00 | 0,5784 | 8198 | 135,0 |
… | … | … | … | … | … |
(95) | 92,4 | 12,30 | 0,3114 | 14784 | 252,0 |
Nominal section, mm2 | Calculated data of AC wire |
Section aluminum/steel, mm2 | Diameter, mm | Electric resistance of 1 km of direct current wire at 20°С,Ohm, not more | Explosive effort of a wire, N, not less | Mass of 1 km of wire, kg |
Wires | Steel core | Aluminum part | steel core |
(10/1,8) | 10,6/1,77 | 4,5 | 1,5 | 2,7064 | 4089 | 28,9 | 13,8 |
(16/2,7) | 16/2,69 | 5,6 | 1,9 | 1,7818 | 6220 | 44,0 | 20,9 |
(25/4,2) | 24,9/4,15 | 6,9 | 2,3 | 1,1521 | 9296 | 67,9 | 32,4 |
(35/6,2) | 36,9/6,15 | 8,4 | 2,8 | 0,7774 | 13524 | 100,0 | 48,0 |
… | … | … | … | … | … | … | … |
(95/16) | 95,4/15,9 | 13,5 | 4,5 | 0,3007 | 33369 | 261,0 | 124 |
Nominal section, mm2 | Calculated data of M wire |
Section, mm2 | Wire diameter, mm | Electric resistance of 1 km of direct current wire at 20°С, Ohm, not more | Explosive effort of a wire, N, not less | Mass of 1 km of wire, kg |
4 | 3,94 | 2,2 | 4,6009 | 1661 | 35 |
6 | 5,85 | 2,8 | 3,0701 | 2467 | 52 |
10 | 9,89 | 3,6 | 1,8197 | 3881 | 88 |
16 | 15,90 | 5,1 | 1,1573 | 6031 | 142 |
25 | 24,90 | 6,4 | 0,7336 | 9463 | 224 |
… | … | … | … | … | … |